Modern, static UPS power systems are broadly classified into three design architectures: on-line, off-line and line interactive. This post describes and compares the three types of uninterruptible power supplies and explains why – for truly critical loads – on-line UPS topology is the only acceptable approach.
Assuming that the uninterruptible power supply design uses batteries which remain as the most popular form of energy storage for back up power supply applications – then it always has three key elements to support these, irrespective of the topology: a charger or rectifier/charger, an inverter, and a static switch. However, the way in which these building blocks are deployed does depend on whether they are off-line or on-line UPS topology.
In an off-line UPS power supply, the critical load is powered directly from the raw AC mains input during normal operation. The incoming power bypasses the UPS power conversion elements to connect the load directly with the static switch. This only transfers the load to the inverter output if the mains power supply fails, transgresses preset voltage or frequency limits, or exhibits some other anomaly.
This uninterruptible power supply topology can appeal to some users because it offers cost savings. As the UPS conversion stages are bypassed during normal operation. UPS power systems operate more efficiently, with lower losses and a reduced cooling requirement. Capital costs are also reduced because off-line uninterruptible power supplies can use lower-rated components and does not need a power rectifier.
But set against this is the consideration that throughout normal operation the load will be subjected to a waveform that is not closely regulated and exposed to disturbances arriving from the utility mains. Although such UPS power systems usually have a degree of spike suppression and rf (radio frequency) filtering, a level of exposure remains. Additionally, there is an inevitable load supply break of typically two to 10 ms while the static switch transfers the load between the inverter output and the mains power supply.
Line-interactive UPS systems are off-line uninterruptible power supply variants that attempt to offer a higher level of performance than conventional types by adding voltage regulation features in the bypass line. The two most popular line-interactive UPS system designs employ either a buck/boost transformer or a ferroresonant transformer. They improve on conventional off-line uninterruptible power supply systems by providing a degree of automatic voltage regulation, and possibly by reducing UPS battery usage and associated degradation to battery life.
An on-line uninterruptible power supply system is fundamentally different from the off-line types in that, during normal operation, mains power flows through the rectifier/charger and inverter before reaching the load. This UPS design is sometimes referred to as a double-conversion UPS power system due to its two conversion stages of AC-DC and DC-AC. This offers the greatest degree of critical supply integrity in that the load is supplied with processed, well-regulated power supply at all times. The load is also protected from input supply aberrations because of the rectifier and inverter act as a barrier to mains-borne noise and transient voltage excursions.
If the input power supply goes outside a preset voltage range (typically +10% to -20%) or frequency or suffers a total failure, the inverter continues operating from back up battery power supply. The event is totally transparent to the load as there is no transfer operation involved.
For these reasons, most data centre owners, or other users responsible for ICT operations that are mission-critical, will always select on-line UPS solutions. They are the only approach that offers truly comprehensive protection to the load at all times. Their extra cost becomes insignificant when compared with the consequences of a catastrophic uninterruptible power supply system failure – which is a likely outcome of mains power supplies problems being allowed to reach the critical load.
If you require more information on any of our uninterruptible power supplies services or products please use our contact page or call 0800 731 3269.